Automated Logic Clamp-On Units are designed to monitor water temperature in retrofit or filled pipe applications. They fit around the outside of a pipe, greatly reducing installation cost. They measure the water temperature by sensing the surface temperature of the pipe.

The bendable copper sensing plate forms to the curvature of the pipe. An adjustable hose clamp holds the unit in place around the pipes up to 11.4cm.

These units have etched Teflon leadwires and double encapsulated sensors and come with a steel J-Box Enclosure, a plastic BAPI-Box 4, or a plastic BAPI-Box 2 Enclosure.

PART NUMBER AND DESCRIPTION
Part Number Description
NSB-10K-2-S-A Clamp-On with 10K-2 Thermistor and J-Box Enclosure
NSB-10K-2-S-BB2-A Clamp-On with 10K-2 Thermistor and BAPI-Box 2 Enclosure
NSB-10K-2-S-BB4-A Clamp-On with Temperature Sensor, BAPI-Box 4 Enclosure
SPECIFICATIONS
Enclosure Material and Enclosure Rating:
  • J-Box: Galvanized Steel, IP20, NEMA 1
  • BAPI-Box 2: Polycarbonate, IP66, NEMA 4
  • BAPI-Box 4: Nylon & Plastic, IP10
    • (IP44 rating with Knockout Plug)
Environmental Operation Range:
  • Temp. Sensor: -85 to 212°F |-65 to 100°C
  • Humidity: 0 to 95%, non-condensing
10K-2 Thermistor Sensor:
  • Resistance: 10 kΩ @ 25°C, -55 to 150°C range
  • Standard Accuracy: 0.2°C (±0.36°F) at 0 to 70°C
  • Dissipation Constant: 2.7 mW/°C
  • Stability(drift): Less than ±0.1°C (0.18°F) drift over
Part Number Description
NSB-10K-2-S-A Clamp-On with 10K-2 Thermistor and J-Box Enclosure
NSB-10K-2-S-BB2-A Clamp-On with 10K-2 Thermistor and BAPI-Box 2 Enclosure
NSB-10K-2-S-BB4-A Clamp-On with Temperature Sensor, BAPI-Box 4 Enclosure
Enclosure Material and Enclosure Rating:
  • J-Box: Galvanized Steel, IP20, NEMA 1
  • BAPI-Box 2: Polycarbonate, IP66, NEMA 4
  • BAPI-Box 4: Nylon & Plastic, IP10
    • (IP44 rating with Knockout Plug)
Environmental Operation Range:
  • Temp. Sensor: -85 to 212°F |-65 to 100°C
  • Humidity: 0 to 95%, non-condensing
10K-2 Thermistor Sensor:
  • Resistance: 10 kΩ @ 25°C, -55 to 150°C range
  • Standard Accuracy: 0.2°C (±0.36°F) at 0 to 70°C
  • Dissipation Constant: 2.7 mW/°C
  • Stability(drift): Less than ±0.1°C (0.18°F) drift over