Outside Air Temp and Humidity
Humidity control is an important aspect of any climate control system. Therefore, humidity sensors must be both accurate and dependable. Automated Logic’s humidity sensors are prescreened for accuracy, eliminating the need for field calibration. The outside air units are also extremely dependable, with a watertight (IP66), UV-resistant polycarbonate enclosure.
Automated Logic outside air temperature and humidity sensors have etched Teflon™ leadwires and are built to withstand high humidity and condensation and perform under real world conditions. This is especially important in an outside air sensor which can be exposed to rain, snow, and large temperature swings.
Part Number and Description
Part Number | Description |
---|---|
NSB-10K-2-H200-O-BB2-A | 2%RH Outside Air Temp & Humidity Sensor with a Box Enclosure 10K-2 Thermistor in a Box enclosure , interchangeable 0 to 5 or 4 to 20 mA %RH output |
Specifications
Power:
- 10 to 35 VDC or 12 to 27 VAC (0 to 5 VDC %RH output)
- 22 mA max. DC or 0.53 VA max. AC
- Temp: -40 to 70 °C | -40 to 158 °F
- 0 to 100% RH
- UV-resistant polycarbonate, UL 94, V-0
- Enclosure Rating: IP66, NEMA 4
Humidity Sensor
- Capacitive 2% or 3% RH (10 to 90% RH @ 23°C)
10K-2 Thermistor Sensor
- Resistance: 10 kΩ @ 25°C, -55°C to 150°C range
- Standard Accuracy: 0.2°C (±0.36°F) at 0 to 70°C
- Dissipation Constant: 2.7 mW/°C
- Stability(drift): Less than ±0.1°C (0.18°F) drift over 10 years.
Part Number | Description |
---|---|
NSB-10K-2-H200-O-BB2-A | 2%RH Outside Air Temp & Humidity Sensor with a Box Enclosure 10K-2 Thermistor in a Box enclosure , interchangeable 0 to 5 or 4 to 20 mA %RH output |
Power:
- 10 to 35 VDC or 12 to 27 VAC (0 to 5 VDC %RH output)
- 22 mA max. DC or 0.53 VA max. AC
- Temp: -40 to 70 °C | -40 to 158 °F
- 0 to 100% RH
- UV-resistant polycarbonate, UL 94, V-0
- Enclosure Rating: IP66, NEMA 4
- Capacitive 2% or 3% RH (10 to 90% RH @ 23°C)
- Resistance: 10 kΩ @ 25°C, -55°C to 150°C range
- Standard Accuracy: 0.2°C (±0.36°F) at 0 to 70°C
- Dissipation Constant: 2.7 mW/°C
- Stability(drift): Less than ±0.1°C (0.18°F) drift over 10 years.